1.1 Generators
The generator or alternator is the important element of power
system. It is of synchronous type and is driven by turbine thus
converting mechanical energy into electrical energy. The two main parts
of generator are stator and rotor. The stationary part is called stator
or armature consisting of conductors embedded in the slots. The
conductors carry current when load is applied on the generator. The
rotating part or rotor is mounted on the shaft and rotates inside the
stator. The winding on rotor is called field winding. The field winding
is excited by d.c. current. This current produces high m.m.f. The
armature conductors react with the m.m.f. produced by the field winding
and e.m.f. gets induced in the armature winding. The armature conductors
carry current when the load is connected to an alternator. This current
produces its own m.m.f. This m.m.f. interacts with the m.m.f. produced
by the field winding to generate an electromagnetic torque between
stator and rotor.
The d.c. current required for field winding is supplied through
exciter which is nothing but a generator mounted on the same shaft on
which alternator is mount. The separate d.c. source may also be used
sometimes to excite the field windings through brushes bearing o slip
rings.
The generators are driven by prime mover which is normally a
steam or hydraulic turbine. The electromagnetic torque developed in the
generator while delivering power opposes the torque provided by the
prime mover.
With properly designed rotor and proper distribution of stator
windings around the armature, it is possible to get pure sinusoidal
voltage from the generator. This voltage is called no load generated
voltage or generated voltage. The representation of generator is shown
in the Fig. 1.
Fig. 1 Representation of alternator |
1.2 Transformer
For stepping up or down the system voltage, power transformers
are used in the substations. At generating end, the voltage is only
stepped up for transmission of power while at all the subsequent
substations the voltage is gradually stepped down to reach finally to
working voltage level.
Instead of using a bank of 3 single phase transformers, a single
three phase transformer is used nowadays. The advantages of using this
transformer is the easiness in its installation and only one three phase
load tap changing mechanism can be used.
Generally naturally cooled, oil immersed, two winding, three
phase transformers upto the rating of 10 MVA are installed upon lengths
of rails fixed on concrete slabs having foundations 1 to 1.5 m deep. For
more than 10 MVA ratings, forced oil, water cooling and air blast
cooling type may be used. The tap changers are used for regulating the
voltage of transformers.
1.3 Transmission Line
The transmission line forms the connecting link between the
generating stations and the distribution systems. It carries the power
generated by generating stations and makes it available for distribution
through distribution network.
Any electrical transmission line has four major parameters which
are important from the point view of its proper operation. These
parameters are namely resistance, inductance, capacitance and
conductors.
The resistance and inductance is uniformly distributed along the
line. It forms series impedance. The resistance of a line is responsible
for power loss. It is expected that the resistance of a line should be
as low as possible so that the transmission system will be more
efficient. Due to linkage, the conductor is associated with inductance
which is distributed along the length of the line. For analysis, both
resistance and inductance are assumed to be lumped.
The capacitance also exists between the conductors and is the
charge on the conductors per unit of potential difference between them.
The conductance between conductors or between conductors and the ground
is due to leakage current at the insulators of overhead lines and
through the insulation of cables. The leakage at conductors is
negligible so the conductance between conductors of an overhead line is
taken as zero. The conductance and capacitance between conductors of a
single phase line or from conductor to neutral of a three phase line
form the shunt admittance.
Depending upon the length of the transmission line it is
classified as short transmission line, medium transmission line and long
transmission line. For short line, its length is small so capacitance
effects are small and are neglected.
1.4 Bus Bars
Bus bars are the common electrical component that connect
electrically number of lines which are operating at the same voltage
directly. These bars are of either copper or aluminium generally of
rectangular cross-section. They can be of other shapes such as round
tubes, round solid bars or square tubes.
The outdorr bus bars, pipes are used. The pipes are also used for
making connections among different components. The pedestal insulators
support the bus bars and the connections. The equipments and bus bars
are spared out and it requires large space. The clearance remain
constant s the bus bars are rigid.
It has following advantages.1) The maintenance is easy as bus bars and connections are not very high from ground.
2) As pipe diameter is large, the corona loss is less.
3) Reliability is more than strain type.
Following are its limitations.
1) Larger area is required.
2) It requires comparatively high cost.
In strain type, bus bars are an overhead system of wires between
two supporting structure and supported by strain type insulators. As per
the size of the conductor, the stringing tension can be limited (500 -
900 kg).
The advantage of this type is its economy and its recommended presently due to general shortage of aluminium pipes.
The material used in case of rigid type bus bars is aluminium
pipes. The general sizes of pipes commonly used for voltage are as given
below.
33 kv 40 mm
66 kv 65 mm
132 kv 80 mm
220 kv 80 mm
400 kv 100 mm
Due to rapid oxidization of aluminium, proper care must be taken
while doing connections. In order to avoid strain of supporting
insulators due to thermal expansion or contraction of pipe, joints
should be provided.
In case of strain type arrangement, material used is ACSR
(Aluminium conductors with steel reinforcement) and all aluminium
conductors. For high ratings of bus bars bundled conductors are used.
The commonly used sizes are as below.
66 kv 37/2.79 mm ACSR
132 kv 37/4.27 mm ACSR
220 kv 61/3.99 mm ACSR
400 kv 61/7.27 mm ACSR in duplex
1.5 Circuit Breakers
The circuit breakers are used to open or close a circuit under
normal and faulty conditions. It can be designed in such a way that it
can be manually operated or by remote control under normal conditions
and automatically operated during fault. For automatic operation, relay
circuit is used.
The circuit breakers are essential as isolators cannot be used to
open a circuit under normal conditions as it has no provision to quench
arc that is produced after opening the line. It has perform following
functions.
i) Full load current is to be carried continuously.ii) Opening and closing the circuit on no load.
iii) Making and breaking the normal operating current.
iv) Making and breaking the fault currents of magnitude upto which it is designed for.
Upto 66 KV voltages, bulk oil circuit breaker are used. Voltages
greater than 66 KV, low oil circuit breaker are used. For still high
voltages, air blast, vacuum or SF6 circuit breakers are used.
1.6 Isolators
In order to disconnect a part of the power system for maintenance
and repair purposes, isolating switches are used. These are operated
after switching off the load by means of a circuit breaker. The
isolators are connected on the both sides of circuit breakers. Thus to
open isolators, circuit breakers are to be opened first.
An isolator is essentially a knife switch and is designed to open
a circuit under no load that is lines in which are connected should be
carrying any current.
Use of isolators in a substation is shown in the Fig. 2.Fig. 2 Line diagram of substation with use of isolating switches |
As shown in thew Fig. 2, there are 5 sections. With the help of
isolators, each section can be disconnected for repair and maintenance.
If it is required to do maintenance in section 4, then the circuit
breaker in that section is to be opened first and then open the isolator
3 and 4. Thus section 4 is open for maintenance. After maintenance, the
isolators 3 and 4 are to be closed first and then circuit breaker is
closed.
In some cases, isolators are used as circuit breaking devices.
But it is limited by particular conditions such are power rating of
given circuit. The isolators are of two types viz single pole and three
pole isolators.
No comments:
Post a Comment