1.1 Generators 
       The generator or alternator is the important element of power 
system. It is of synchronous type and is driven by turbine thus 
converting mechanical energy into electrical energy. The two main parts 
of generator are stator and rotor. The stationary part is called stator 
or armature consisting of conductors embedded in the slots. The 
conductors carry current when load is applied on the generator. The 
rotating part or rotor is mounted on the shaft and rotates inside the 
stator. The winding on rotor is called field winding. The field winding 
is excited by d.c. current. This current produces high m.m.f. The 
armature conductors react with the m.m.f. produced by the field winding 
and e.m.f. gets induced in the armature winding. The armature conductors
 carry current when the load is connected to an alternator. This current
 produces its own m.m.f. This m.m.f. interacts with the m.m.f. produced 
by the field winding to generate an electromagnetic torque between 
stator and rotor.
       The d.c. current required for field winding is supplied through 
exciter which is nothing but a generator mounted on the same shaft on 
which alternator is mount. The separate d.c. source may also be used 
sometimes to excite the field windings through brushes bearing o slip 
rings.
       The generators are driven by prime mover which is normally a 
steam or hydraulic turbine. The electromagnetic torque developed in the 
generator while delivering power opposes the torque provided by the 
prime mover.
       With properly designed rotor and proper distribution of stator 
windings around the armature, it is possible to get pure sinusoidal 
voltage from the generator. This voltage is called no load generated 
voltage or generated voltage. The representation of generator is shown 
in the Fig. 1.
![]()  | 
| Fig. 1 Representation of alternator | 
1.2 Transformer
       For stepping up or down the system voltage, power transformers 
are used in the substations. At generating end, the voltage is only 
stepped up for transmission of power while at all the subsequent 
substations the voltage is gradually stepped down to reach finally to 
working voltage level.
       Instead of using a bank of 3 single phase transformers, a single 
three phase transformer is used nowadays. The advantages of using this 
transformer is the easiness in its installation and only one three phase
 load tap changing mechanism can be used.
       Generally naturally cooled, oil immersed, two winding, three 
phase transformers upto the rating of 10 MVA are installed upon lengths 
of rails fixed on concrete slabs having foundations 1 to 1.5 m deep. For
 more than 10 MVA ratings, forced oil, water cooling and air blast 
cooling type may be used. The tap changers are used for regulating the 
voltage of transformers.
1.3 Transmission Line
      The transmission line forms the connecting link between the 
generating stations and the distribution systems. It carries the power 
generated by generating stations and makes it available for distribution
 through distribution network.
       Any electrical transmission line has four major parameters which 
are important from the point view of its proper operation. These 
parameters are namely resistance, inductance, capacitance and 
conductors.
       The resistance and inductance is uniformly distributed along the 
line. It forms series impedance. The resistance of a line is responsible
 for power loss. It is expected that the resistance of a line should be 
as low as possible so that the transmission system will be more 
efficient. Due to linkage, the conductor is associated with inductance 
which is distributed along the length of the line. For analysis, both 
resistance and inductance are assumed to be lumped.
        The capacitance also exists between the conductors and is the 
charge on the conductors per unit of potential difference between them. 
The conductance between conductors or between conductors and the ground 
is due to leakage current at the insulators of overhead lines and 
through the insulation of cables. The leakage at conductors is 
negligible so the conductance between conductors of an overhead line is 
taken as zero. The conductance and capacitance between conductors of a 
single phase line or from conductor to neutral of a three phase line 
form the shunt admittance.
       Depending upon the length of the transmission line it is 
classified as short transmission line, medium transmission line and long
 transmission line. For short line, its length is small so capacitance 
effects are small and are neglected.
1.4 Bus Bars
       Bus bars are the common electrical component that connect 
electrically number of lines which are operating at the same voltage 
directly. These bars are of either copper or aluminium generally of 
rectangular cross-section. They can be of other shapes such as round 
tubes, round solid bars or square tubes.
       The outdorr bus bars, pipes are used. The pipes are also used for
 making connections among different components. The pedestal insulators 
support the bus bars and the connections. The equipments and bus bars 
are spared out and it requires large space. The clearance remain 
constant s the bus bars are rigid.
       It has following advantages.1) The maintenance is easy as bus bars and connections are not very high from ground.
2) As pipe diameter is large, the corona loss is less.
3) Reliability is more than strain type.
Following are its limitations.
1) Larger area is required.
2) It requires comparatively high cost.
       In strain type, bus bars are an overhead system of wires between 
two supporting structure and supported by strain type insulators. As per
 the size of the conductor, the stringing tension can be limited (500 - 
900 kg).
       The advantage of this type is its economy and its recommended presently due to general shortage of aluminium pipes.
       The material used in case of rigid type bus bars is aluminium 
pipes. The general sizes of pipes commonly used for voltage are as given
 below.
33 kv                              40 mm
66 kv                              65 mm
132 kv                             80 mm
220 kv                             80 mm
 400 kv                             100 mm
       Due to rapid oxidization of aluminium, proper care must be taken 
while doing connections. In order to avoid strain of supporting 
insulators due to thermal expansion or contraction of pipe, joints 
should be provided.
       In case of strain type arrangement, material used is ACSR 
(Aluminium conductors with steel reinforcement) and all aluminium 
conductors. For high ratings of bus bars bundled conductors are used. 
The commonly used sizes are as below.
66 kv                   37/2.79 mm                      ACSR
132 kv                  37/4.27 mm                     ACSR
220 kv                  61/3.99 mm                     ACSR
              400 kv                  61/7.27 mm                     ACSR in duplex
1.5 Circuit Breakers
       The circuit breakers are used to open or close a circuit under 
normal and faulty conditions. It can be designed in such a way that it 
can be manually operated or by remote control under normal conditions 
and automatically operated during fault. For automatic operation, relay 
circuit is used.
       The circuit breakers are essential as isolators cannot be used to
 open a circuit under normal conditions as it has no provision to quench
 arc that is produced after opening the line. It has perform following 
functions.
i) Full load current is to be carried continuously.ii) Opening and closing the circuit on no load.
iii) Making and breaking the normal operating current.
iv) Making and breaking the fault currents of magnitude upto which it is designed for.
       Upto 66 KV voltages, bulk oil circuit breaker are used. Voltages 
greater than 66 KV, low oil circuit breaker are used. For still high 
voltages, air blast, vacuum or SF6 circuit breakers are used.
1.6 Isolators 
       In order to disconnect a part of the power system for maintenance
 and repair purposes, isolating switches are used. These are operated 
after switching off the load by means of a circuit breaker. The 
isolators are connected on the both sides of circuit breakers. Thus to 
open isolators, circuit breakers are to be opened first.
       An isolator is essentially a knife switch and is designed to open
 a circuit under no load that is lines in which are connected should be 
carrying any current.
       Use of isolators in a substation is shown in the Fig. 2.![]()  | 
| Fig. 2 Line diagram of substation with use of isolating switches | 
      As shown in thew Fig. 2, there are 5 sections. With the help of 
isolators, each section can be disconnected for repair and maintenance. 
If it is required to do maintenance in section 4, then the circuit 
breaker in that section is to be opened first and then open the isolator
 3 and 4. Thus section 4 is open for maintenance. After maintenance, the
 isolators 3 and 4 are to be closed first and then circuit breaker is 
closed.
       In some cases, isolators are used as circuit breaking devices. 
But it is limited by particular conditions such are power rating of 
given circuit. The isolators are of two types viz single pole and three 
pole isolators.


No comments:
Post a Comment