1.1 Comparison of C.T. and P.T.
The comparison of C.T. and P.T. is given in the following table,
1.2 Ratios of Instrument Transformers
The various ratios defined for the instrument transformer are,
1. Actual ratio (R)
The actual transformation ratio is defined as the ratio of the
magnitude of the actual primary phasor to the corresponding magnitude of
actual secondary phasor.
The actual ratio is also called transformation ratio.
2. Nominal ratio (Kn)
The nominal ratio is defined as the ratio of rated primary
quantity to the rated secondary quantity, either current or voltage.
3. Turns ratio (n)
1.2.1 Ratio Correction Factor (RCF)
It is the ratio of transformation i.e. actual ratio to the nominal ratio.
... RCF = R/
i.e. R = RCF x Kn
The ratio which is indicated on the name plate of a transformer is always its nominal ratio.
1.3 Errors in Instrument Transformers
For an instrument transformers, it is necessary that the
transformation ratio must be exactly equal to turns ratio and phase of
the secondary terms (voltage and current) must be displaced by exactly
180o from that of the primary terms (voltage and current).
Two types of errors affect these characteristics of an instrument
transformer which are,
1. Ratio error
2. Phase angle error
1.3.1 Ratio Error
In practice it is said that current transformation ratio I2/I1 is equal to the turns ratio N1/N2.
But actually it is not so. The current ratio is not equal to turns
ratio because of magnetizing and core loss components of the exciting
current. It also gets affected due to the secondary current and its
power factor. The load current is not a constant fraction of the primary
current. Similarly in case of potential transformers, the voltage
ratio V2/V1 is also not exactly equal to V2/V1 due
to the factors mentioned above. Thus the transformation ratio is not
constant but depends on the load current, power factor of load and
exciting current of the transformer. Due to this fact, large error is
introduced in the measurements done by the instrument transformers. Such
an error is called ratio error.
The ratio error is defined as,
1.3.2 Phase Angle Error
In the power measurements, it is must that the phase of secondary current is to be displaced by exactly 180o
from that of the primary current for C.T. While the phase of secondary
voltage is to be displaced by exactly from that of the primary voltage,
for P.T. But actually is is not so. The error introduced due to this
fact is called phase angle error. It denoted by angle θ by which the
phase difference between primary and secondary is different from 180o.
The phase angle error is given by,
Approximate results : In practice, the load are inductive and is positive and very small.
... sinδ ≈ 0 and cosδ ≈ 1 hence the equations (4) and (7) becomes,
Interms of Ip, these can be written using n = Ip/Is.
1.4 Characteristic of Current Transformers
Let us steady the effect of various parameters on the characteristics of current transformers,
1. Effect of power factor of secondary circuit
The p.f. of the secondary circuit depends on the p.f. of the
burden on secondary. This directly affects the two errors of the
transformer.
a. Ratio error : For all inductive loads,δ is positive hence
sin(δ + α) is positive hence actual ratio R is always greater than the
turns ratio n. Foe capacitive burdens, is negative and R is less than
the turns ratio.
b. Phase angle error : When load is inductive and is small positive then θ is positive. But as δ approaches 90o as load becomes highly inductive then θ becomes negative. For capacitive load, δ is negative and θ is always positive.
2. Effect of change in Ip
The Ip and Is are directly related thus as Ip changes, Is also changes. For low values of Ip, Io is dominating thus Im and Ic are also dominating parts of Ip. Thus errors are higher. As Ip increases, part of Io becomes insignificant from Ip hence Ic and Im also are less significant compared to Ip i.e. Is. Thus errors are less.
3. Effect of change in burden secondary
The secondary winding circuit burden increases means volt ampere
rating increases. Due to increased current, secondary flux increases
which induce more voltage on secondary. Thus both Im and Ic increases to keep flux constant. Due to this, errors also increases. Thus more secondary burden means more errors.
4. Effect of change in frequency
If frequency is increased at constant voltage then the flux and flux density decreases. Thus there is reduction in Im and Ic hence errors also get reduced.
1.5 Characteristics of Potential Transformers
Let us study the effect of various parameters on the characteristics of potential transformers.
1. Effect of power factor of secondary circuit
The p.f. of secondary circuit depends on the p.f. of the
secondary burden. As p.f. decreases, angle Δ increases. This shifts Ip towards Io, as seen from the phasor diagram. Thus Vp and Vs becomes almost in phase with Ep and Es respectively. Thus Vp becomes more compared to Ep but as Vp in constant as supply voltage., the result is the reduction in Ep. Similarly the voltage Vs also reduces compared to Es. Hence from equation (11) it is clear that, R increases as Vs decreases due to decreases due to decrease in the p.f. of secondary circuit. While Vs advances in phase and Vp retards hence negative phase angle reduces as lagging p.f. of secondary decreases.
2. Effect of change in burden on secondary
The change in burden on secondary changes the secondary current
and secondary VA. As the secondary current increases, primary current
increases. This increases the voltage drops. For constant Vp, Vs decreases. This increases the transformation ratio R. Thus ratio error increases as the secondary current i.e. burden increases.
Due to increased voltage drop, Vp advances while Vs retards in phase. Thus the phase angle between Vp and Vs increases and becomes more negative as the secondary current increases.
3. Effect of change in frequency
If frequency is increased at constant voltage then the flux and flux density decreases. This reduces the values of Im, Ic and hence Io.
This tends to reduce errors. But increase in frequency increase the
leakage reactance increasing the voltage drops. This increases the ratio
and ratio error. This effects are opposite to each other and the
resultant effect depends on relative values of Io and the leakage reactance.
While the phase angle increases due to increase in leakage reactance as well as decrease in Io.
4. Effect of primary voltage
The primary voltage is practically constant and there is hardly
any significant change it hence there is no significant change in the
errors.
1.6 Reduction of Errors in Instrument Transformers
The ratio and phase angle error can be minimized by using following methods:
1. Reduction the core loss and magnetizing components of Io
The equations of ratio and phase angle errors show that the
errors depend on the core loss and magnetizing components of no load
current Io. The following precautions are taken to reduce Ic and Im,
1. Choosing low reluctance core.
2. Using material of high permability.
3. Providing smaller magnetic paths to the flux.
4. Using large cross section of the core.
5. Keeping flux density in the core to low value.
6. Taking suitable precautions while designing the assembly and interleaving the core.
2. Reduction of resistance and leakage reactance
The errors depends on the voltage drops which are inturn depend on the values of resistance and leakage reactance.
The resistance can be reduced by increasing cross-section of conductors and decreasing the length of the mean turn.
The leakage reactances depend on the leakage fluxes.
Note : Thus mutual coupling between the windings must be high hence windings must be as close as possible.
Similarly keeping flux density as high as practicable, the number
of turns required are less hence leakage reactances get reduced.
3. Providing turns compensation
Thus on no load, actual ratio exceeds by some factor. The remedy
for this is to reduce the primary turns or increasing the number of
secondary turns. Thus for one particular value of load, the actual ratio
can be made equal to nominal ratio. This reduces the ratio error over
the entire range of the burden. This is called turns compensation.
However, the turns compensation does not affect the phase angle θ.
1.7 Advantages and Disadvantages of Instrument Transformer
The advantages of instrument transformers can be listed as,
1. The normal range voltmeter and ammeter can be used along with these transformers to measure high voltage and currents.
2. The rating of low range meter can be fixed irrespective of the value of high voltage or current to be measured.
3. These transformer isolate the measurement from high voltage and
current circuits. This ensures safety of the operator and makes the
handling of the equipments very easy and safe.
4. These can be used for operating many types of protecting devices such as relay or pilot lights.
5. Several instruments can be fed economically by single transformer.
Disadvantages :
The only disadvantage of these instrument transformers is that they can
be used only for a.c. circuits and not for d.c. circuits.
Well written blog you shared. keep sharing. thank you.
ReplyDeleteSMPS Transformer Manufacturer in India | Toroidal Transformer in India
Very informative blog you shared. keep posting.Aerospace wiring harness manufacturer in India | Toroidal chokes manufacturers in India
ReplyDeleteThanks for sharing this informative post with us.
ReplyDeleteIf you are searching Best Transformer Manufacturers in India, and want to buy any kinds of Transformers so, Trutech Products is one of the prominent Transformer Manufacturers In Mumbai.
Transformer Manufacturers in Pune